This guide covers all aspects of MCC design including functional unit sizing, busbar and feeder calculations, withdrawable vs fixed configurations, communication architecture, and layout optimization for industrial motor control applications.
Motor Control Center (MCC) Design Guide
Comprehensive guide to MCC design and engineering.

Need help applying this to your project?
Our engineering team can help you implement these concepts in your panel design. Contact Patrion for a consultation.
Frequently Asked Questions
What IEC standard governs Motor Control Center (MCC) assemblies?
Motor Control Centers are typically built as low-voltage switchgear and controlgear assemblies to IEC 61439-1 and IEC 61439-2. These standards define the responsibilities of the original assembly manufacturer, temperature-rise verification, dielectric properties, short-circuit withstand, protective circuits, and clearances/creepage distances. For MCC-specific design, the builder must also ensure compliance with the functional requirements of the installed devices, such as contactors, overload relays, MCCBs, soft starters, and VFDs. In practice, the assembly must be verified for rated current, rated diversity factor, internal separation form, and incoming fault levels. If the MCC is intended for industrial motor feeders, IEC 61439 verification is the key framework, while device-specific standards like IEC 60947-4-1 for contactors and motor-starters remain relevant for component selection and coordination.
How is short-circuit withstand calculated for an MCC?
Short-circuit withstand for an MCC is not guessed; it is verified against the prospective fault current at the installation point and the protective device clearing characteristics. Under IEC 61439, the assembly must have a declared short-circuit rating such as Icc, Icw, or Ipk depending on the design method used. The MCC incoming device may be an MCCB, ACB, or fuse combination, and the downstream feeder units must coordinate with that upstream protective device. Designers often use manufacturer-provided verified combinations or tested assembly data to prove compliance. For motor feeders, the let-through energy of the protective device must not damage busbars, starters, or cabling. If a drive is used, the upstream SCCR and the VFD’s own short-circuit current rating must both be checked. Proper busbar bracing, compartment construction, and fault containment are essential to maintaining the declared rating.
What is the best way to size MCC busbars and feeders?
MCC busbar and feeder sizing starts with continuous current, ambient temperature, enclosure ventilation, and diversity. Under IEC 61439, the rated current of the assembly must be verified at the declared ambient conditions, usually 35°C or 40°C depending on the design. Busbar cross-section is selected to carry the maximum demand current with acceptable temperature rise, taking into account grouping, enclosure layout, and the number of outgoing starters. Copper busbars are common in industrial MCCs, while aluminum may be used where cost and weight are important, provided joints and plating are engineered correctly. Feeder conductors are sized based on motor full-load current, starting duty, overload relay settings, and voltage drop, especially for long cable runs. A good MCC design also considers future expansion, leaving busbar headroom and spare feeder compartments so the lineup can absorb additional loads without derating.
How do you choose between DOL, star-delta, soft starter, and VFD feeders in an MCC?
The feeder choice depends on motor size, load inertia, process requirements, and network limitations. Direct-on-line (DOL) starters are simplest and suitable where inrush current and mechanical shock are acceptable. Star-delta starters reduce starting current and are often used on medium-size pumps and fans, but they require six-lead motors and deliver reduced starting torque. Soft starters provide controlled voltage ramp-up and are preferred when mechanical stress must be minimized without full speed control. Variable frequency drives (VFDs) are used when speed control, energy savings, or precise process control is needed. In an MCC, each option affects heat dissipation, compartment spacing, EMC, and protective coordination. VFD feeders may require line reactors, harmonic mitigation, and shielded motor cables. IEC 60947-4-1 supports starter selection, while the MCC assembly design under IEC 61439 must account for thermal load and segregation so that high-loss feeders do not overheat adjacent units.
What segregation forms are used inside an MCC and why do they matter?
Segregation inside an MCC is used to improve safety, maintainability, and fault containment. IEC 61439 defines internal separation arrangements, commonly referred to as Form 1 through Form 4, with varying levels of separation between busbars, functional units, and terminals. Higher segregation levels can help limit the impact of a fault to a single motor feeder and allow safer maintenance on adjacent sections. For example, a Form 3b or Form 4 arrangement may separate busbars, functional units, and outgoing terminals into distinct compartments, which is common in critical-process plants and high-availability installations. However, more segregation increases enclosure size, cost, and sometimes heat concentration if not ventilated properly. MCC designers must balance uptime requirements with practicality. The selected form should match the fault level, maintenance philosophy, and the need for live testing or replacement of starters, contactors, or VFD modules.
How should thermal management be handled in an MCC with VFDs and soft starters?
Thermal management is a major MCC design issue because electronic feeders such as VFDs and soft starters generate more heat than conventional DOL starters. IEC 61439 requires temperature-rise verification for the complete assembly, not just individual components. Designers should calculate total losses from contactors, overload relays, drives, transformers, control power supplies, and busbars, then ensure the enclosure can dissipate that heat at the declared ambient temperature. Common measures include vertical air ducts, filtered fans, heat exchangers, forced ventilation, and strategic spacing of high-loss units. VFDs often need dedicated compartments or separate ventilated sections to prevent heat from affecting motor starters and control electronics. If harmonic filters or line reactors are used, their losses must be included in the thermal model. Excessive temperature accelerates insulation aging, reduces contactor life, and can cause nuisance trips, so thermal design is as important as short-circuit design in modern MCCs.
What protection devices are typically included in an MCC motor feeder?
A typical MCC motor feeder includes short-circuit protection, overload protection, and a switching device. In many designs, this is an MCCB or fuse-switch combination upstream of a contactor and thermal overload relay, though motor-protective circuit breakers are also common for smaller motors. IEC 60947-4-1 covers contactors and motor-starters, while IEC 60947-2 applies to circuit breakers used as protective devices. The exact arrangement depends on motor starting method, fault level, selectivity requirements, and maintenance strategy. For example, a DOL feeder may use an MCCB, contactor, and overload relay; a VFD feeder may use an upstream breaker plus drive internal protection and motor temperature sensing. Phase loss, single-phasing, overload curve class, and coordination with the motor’s locked-rotor current are critical. Proper discrimination with the upstream incomer protects continuity of service so that a fault in one feeder does not trip the entire MCC.
What tests are required before an MCC can be commissioned?
Before commissioning, an MCC should undergo routine verification and site testing to confirm that the assembly matches its verified design. Under IEC 61439, routine verification includes inspection of wiring, protective bonding, clearances, operation of mechanical interlocks, dielectric tests where applicable, and checking the correctness of labels and settings. For motor feeders, technicians also test control logic, overload relay settings, contactor operation, phase rotation, and emergency stop circuits. Insulation resistance and continuity tests are typically performed on outgoing circuits and control wiring. If VFDs are installed, parameter checks, motor nameplate data entry, and communication network validation should be included. Functional tests should simulate start, stop, trip, and interlock conditions for each feeder. A properly documented commissioning pack with test results, torque records, and as-built drawings is essential for handover and future maintenance. Routine verification does not replace design verification; both are required for a compliant MCC assembly.